Sequencer COMPACT
Technical brochure
FI 72.0467.0118E
Page 31 / 42
Page Sequencer Parameters (2/2)
1: T1: IMPULSE
→
Impulse time on 1 declogging SV
Adjustable from 3 to 255/100 seconds (setting enabled in level 1 & 2)
2: T2: REST
→
Resting time between 2 impulses on SV
Adjustable from 1 to 255 seconds (setting enabled in level 1 & 2)
3:T2A: RESTBis
→
Resting time between 2 impulses on SV Bis
Adjustable from 1 to 255 seconds (setting enabled in level 1 & 2)
T2A Time (always smaller than T2) replaces T2 time if accelerated running is active
(pressure>Threshold of T2A or accelerated declogging input T2A).
4: T3: END OF CYCLE
→
Resting time between 2 declogging cycles
Adjustable from 0 to 255 minutes (setting enabled in level 1 & 2)
0 = inactive
5: T4: AUTO CYCLE
→
If the sequencer did not have declogging cycle during the defined time (in hours),
The running cycle ends up (if stopped during cycle) and one declogging cycle is launched.
Remark: T4 Time is reset at each impulse on any SV.
Adjustable from 0 to 255 hours (setting enabled in level 1 & 2)
0=inactive
The function is active, in accordance to the following point adjustment (6).
6: Condition to run the declogging linked to T4 time. 2 possible choices (setting enabled in level 2):
-whatever is the running order input
-only if the running order input is on
7: Link towards page sequencer parameters (1/2)
8: Link towards main page / synoptic
9: Link towards page Parameters
1
2
3
4
5
7
8
9
6