Installation of the cooler must conform to local electrical rules,
regulations and standards.
Important!
It is a requirement of Seeley International that all
coolers be connected to a dedicated circuit to the distribution
board, with a separate circuit breaker and incorporate a separate
isolation switch in accordance with the local wiring rules.
A 10A socket outlet within one metre of the dropper’s cable exit
hole is required.
The following specifications for the cooler electrical supply
are required:
220 - 240V / 50 or 60Hz Single Phase. (See
nameplate for exact data in cooler)
For CW-6S models:
The electronics module is fitted with a replaceable 15A anti-
surge fuse and an isolation switch that is toggled manually.
WARNING!
Replacing the fuse exposes the operator to high
voltage components. this operation may only be conducted by
a qualified electrician. To replace the fuse: turn off the main
isolator to the cooler, turn off the electronics isolation switch,
remove the electronics cover and replace the fuse located to
the left of the isolation switch.
ELECTRICAL REQUIREMENTS
WARNING!
If the supply cord is damaged, it must be replaced
by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
PUMP
LEFT
PUMP
RIGHT
MOTOR
BOTTOM
POWER
ON / OFF
250V, 15A
F2
DSW
INDIRECT
PUMP
DIRECT
PUMP
SUPPLY
MOTOR
EXHAUST
MOTOR
MOTOR
TOP
MOTOR
TOP
MOTOR
BOTTOM
AIR
SENSOR
CONTROLLER:
MAGIQTOUCH, BMS ETC
SOLENOID
WATER
PROBE
DRAIN
CHLORINATOR
SENSOR
W/CONTROL
ILL2681-B
ILL2681-B
FIELD WIRING DIAGRAM
CONTROL MODULE WIRING DIAGRAM
WATER REQUIREMENTS
Installation of the cooler water supply must conform to
local plumbing rules, regulations and standards.
The following specifications for the cooler water supply are
required:
Water Connection
½
”
BSP
Min Water Pressure
100kPa (15psi)
Max Water Pressure
800kPa (115psi)
Min Water Flow
13 liters/min (3.4 gallons/min)
Max Water Flow
20 liters/min (5.3 gallons/min)
Max Water Temperature 40°C (104°F)
Important!
If the water pressure exceeds maximum
specification then a pressure reducing valve is required and
must be supplied and fitted by the installer.
A permanent water supply is required to be connected to the
cooler. The water connection point is located on the underside of
the cooler, left hand side.
You must install a manual 1/4 turn ball type shut off valve (do not
use a stop cock) in the water supply line adjacent to the cooler,
subject to local plumbing regulations. This allows the water supply
to be isolated whenever work needs to be done on the cooler.
Water connection is via a ½” BSP male to 3/4” BSP female
braided hose (supplied). The 3/4” end connects straight to the
inlet solenoid. Use the ½” BSP male inlet end of hose to connect
to the mains supply.
Always ensure that the water pipe connection does not place
sideways strain onto the float valve.
Important!
In areas subject to freezing, the water supply line to
the cooler requires a drain down facility at the lowest point in the
water supply pipe.
Important!
Flush the water pipe to remove any swarf before
final fitting. Swarf can lodge in the solenoid and float valve,
preventing them from functioning correctly.
ILL3102-A