XRIO
Operating Manual XCx 300 / 500 / 540 Version 09/08
67
[XRIO_C01M04]
Name=RIO 8I 8I/O
; Module name
ID =8
; Module-ID
Type=DIGITAL
; Module class
#IB =4
; 2 input bytes
#QB =2
; 2 input bytes
%IB =6
; first input byte of module, byte address 6
; %IB 6 not debounced
; %IB 7 not debounced
; %IB 8 debounced
; %IB 9 debounced
%QB =4
; first output byte of module, byte address 4
; %QB 4 (dummy!)
; %QB 5
[XRIO_C01M05]
Name=RIO 4AI/4AO 20mA
; Module name
ID =14
; Module-ID
Type=ANALOG
; Module class
#IW =4
; 4 input words
#QW =4
; 4 output words
%IW =10
; first input word of module, address 10
; %IW 10
; %IW 12
; %IW 14
; %IW 16
%QW =6
; %QW 6
; %QW 8
; %QW 10
; %QW 12