Technical data
170
Operating Manual XCx 300 / 500 / 540 Version 09/08
15
Technical data
Power supply
Rated voltage
DC 24 V (19,2 V .. 30 V inclusive 5% residual ripple)
Current consumption
max. 4.5 A (incl. all digital I/O)
Isolation
(to internal electronic)
X1 (RS422)
X2 (digital I/O)
X3 USB
X4 XRIO
X5 CAN
X6 ETH (Ethernet)
X7 PRG (RS232)
yes
yes
no
yes
yes
yes
no
Serial interfaces
RS 232
Programming and diagnosis X7 PRG
RS 422
Operating devices X1
More interfaces
USB
Programming, diagnosis, operating interface X3
ETH (Ethernet)
Programming, diagnosis, operating interface X6
CAN
CANopen bus port
XRIO
Port for the special Schleicher XRIO bus to connect the RIO EC X2
bus coupler
Direct Inputs / Outputs (on X2 Connector)
Outputs
DC 24 V, max. 500 mA, General Purpose
Number
2 (I/O 0, I/O 1)
Switching level
H level
+24 V-EXT - 0,5 V
L level
1 V
Signal delay
<300 μs (Hardware)
Inputs
Number
2 (I/O 0, I/O 1)
Switching level
H level = +11 V bis +30 V
L level = -30 V bis +5 V
Input current
min. H level (+11 V) ≥ 2 mA
max. L level (+5 V) ≤ 2 mA
typ. (+24 V) 8 mA
max. (+30 V) ≤ 15 mA
Signal delay
<100 ns (Hardware)
Trigger
Edge triggering
BUSY contact
DC 24 V, max. 2 A, General Purpose
Number
1
Type
potential-free relay contact, NO