PROFIBUS-DP Modules
130
Operating Manual XCx 300 / 500 / 540 Version 09/08
13.2
Displays and Connections XF-DPM
Display
LED Des.
Colour
Condition
Description
XF-DPM
L1
L2
L3
L4
X61
L1
BF
red
No bus connection (bus fail)
green
Bus connection active
yellow
flashing
Bus connection active,
however no data exchange.
L2
Not used
L3
SYS
yellow
flicking
Hardware error
green
flashing
Ready connecting to bus, however no (not as yet)
bus connection active.
green
flicking
Bus connection error
green
Bus connection active
L4
COM
yellow
Cyclic data exchange active
red
Bus connection error
Connector X61
Pin
Designation
1
nc
not connected
2
nc
not connected
3
RxD/TxD-P
Receive/Transmit Data P
4
CNTR-P
Repeater Control Signal
5
DGND
Data Ground (0 V)
6
VP
Voltage Plus (+5 V)
7
nc
not connected
8
RxD/TxD-N
Receive/Transmit Data N
9
nc
not connected
13.3
Technical Data XF-DPM
Basic data
Interface
PROFIBUS-DP Master
Data transmission rate
up to 12 MBaud
Connection system
Subminiature type D, 9-pin, socket connector
Ambient temperature working range 0°C to 45°C