SHAFT SPEED SUPERVISION AT ROUGH POS CHANGE
The car was not decelerating (still traveling in normal speed) while it was
reaching the shaft end (at KSE) because the wrong number of floors was
counted. Failure in shaft information system.
C1:Bad alignment of floor sensors (KS/KS1) with magnets in shaft
A1:Check alignment of magnets. Check position of floor sensors. Check
for lost magnets. Check magnet to sensors distance.
C2:Bad floor sensor signal transmission
A2:Check general electrical wiring of the floor sensor signal (for
example, connections at KS/KS1, at SDIC7x,..)
C3:Floor sensor (KS/KS1) defect
A3:Replace corresponding floor sensor
C4:Faulty input on the interface board (PCB) for the floor sensor
A4:Replace interface board (SDIC7x)
C5:One or more floor indication magnet of the shaft information system
is/are mounted with wrong magnetic orientation
A5:Check entire shaft for the correct magnetic orientation (N,S) of these
magnets
2138
SHAFT CAR RELEVELING ZONE SIGNAL INVALID
The signal indicating the car releveling zone is invalid (for example,
inconsistent). Failure at hoistway information.
C1:A car releveling zone indicator is missing or not at the correct
position
A1:Check correct position of the corresponding indicators (for example,
alignment of magnets, vanes)
C2:A car releveling zone sensor is defective
A2:Check functionality of corresponding sensor (for example, PHS,
PHNR_U, PHNR_D). Replace it if necessary.
C3:A car releveling zone sensor signal is faulty
A3:Check general wiring of corresponding sensors (for example,
PHNR_U, PHNR_D). Check at optical sensors (for example, PHS,
PHNR_U. PHNR_D) vanes and sensors for dirt and proper shielding from
sunlight (for example, at glass shaft).
C4:Bad data transmission
A4:Some hoistway information system transfer their data via data bus.
Check data bus (e.g CAN) for correct data transmission (for example, bad
shielding of data wire).
2139
SHAFT ROUGH POS MISSMATCH BOTTOM
Failure at the lower hoistway end detection
2160
SHAFT MINIMAL TRAVEL DISTANCE
C1:While validating the RAM shaft image at the application startup, a too
small travel distance (< 300 mm) between the levels is detected.
A1:Redo: Learning trip
2161
SHAFT INTOLERABLE FLAG LENGTH
C1:At application startup (reset): While setting up the levels in the RAM
shaft image an intolerable flag length is detected.
A1:Check: for rope slippage. Check: encoder. Redo: learning trip.