ALWAYS MAINTAIN REQUIRED CLEARANCES (TO NEARBY COMBUSTIBLES TO
PREVENT FIRE HAZARD. DO NOT FILL AIR SPACES WITH INSULATION. ALL VENTING
COMPONENTS MUST MAINTAIN 1” (25 MM) CLEARANCE TO COMBUSTIBLE
MATERIALS.
THE GAS INSERT AND VENT SYSTEM MUST BE VENTED DIRECTLY TO THE OUTSIDE
OF THE BUILDING AND NEVER BE ATTACHED TO A CHIMNEY SERVING A SEPARATE
SOLID FUEL OR GAS-BURNING APPLIANCE, EACH DIRECT VENT APPLIANCE MUST
USE ITS OWN SEPARATE VENT SYSTEM. COMMON VENTS ARE PROHIBITED.
REFER TO THE MANUFACTURER’S INSTRUCTIONS INCLUDED WITH THE VENTING
SYSTEM FOR COMPLETE INSTALLATION PROCEDURES.
The horizontal termination must not be recessed into the exterior wall or siding.
Horizontal vent runs must rise ¼” per foot toward the vent termination.
Clearances around the vent termination must be maintained.
For installations using Simpson Duravent pipe, parallel installations with minimum wall clearance
have restricted access for connecting the Horizontal vent cap straps to the vent pipe. See the manu-
facturer’s instructions for recommended installation procedures.