EQJW146F002 EN
131
Appendix
F
Function
WE
Anl
Comments
Function block parameters: value range (default setting)
09 Flash adapta-
tion
0
Not sys-
tems Anl.
1.5, 1.6,
3.x, 16.x
CO1 > F09 - 1: Flash adaptation of flow temperature
(only with CO1 > F01 - 1)
Function block parameters:
Cycle time: 0 or 1 to 100 min (20 min)
KP (gain): 0.0 to 25.0 (0.0)
11 Four-point
characteristic
0
Not Anl
1.5, 1.6
CO1 > F11 - 1: Four-point characteristic (only with CO1 >
F08 - 0)
CO1 > F11 - 0: Gradient characteristic
12 Control mode
(three-step)
1
All*
CO1 > F12 - 1: Three-step control
Function block parameters:
KP (gain): 0.1 to 50.0 (2.0)
Tn (reset time): 1 to 999 s (120 s)
TV (derivative-action time): 0 to 999 s (0 s)
TY (valve transit time): 15, …, 240 s (35 s)
CO1 > F12 - 0: On/off control
Function block parameters:
Hysteresis: 1.0 to 30.0 °C (5.0 °C)
Min. ON time: 0 to 10 min (2 min)
Min. OFF time: 0 to 10 min (2 min)
13 Damping
0
All*
CO1 > F13 - 1: OPEN signal damping (only with CO1 >
F12 - 1)
Function block parameters:
Max. system deviation: 3.0 to 10.0 °C (3.0 °C)
14 Enable
0
All*
CO1 > F14 - 1: Release RK1 at BI1; FG1 has no function
Function block parameters:
Active when BI = ON, OFF (ON)
15 Demand pro-
cessing
0
All*
CO1 > F15 - 1: Demand processing in RK1
Note: How the demand is processed depends on the configura-
tion of CO1 > F16 and CO1 > F17.
16 Demand pro-
cessing, 0 to
10 V
Terminals 11/12
0
All*
CO1 > F16 - 1: Demand processing with 0 to 10 V signal (only
with CO1 > F15 - 1 and CO1 > F17 - 0)
Function block parameters:
Lower transmission range: 0 to 150 °C (0 °C)
Upper transmission range: 0 to 150 °C (120 °C)