EQJW146F002 EN
91
Functions of the heating circuit
Functions
WE
Configuration
Outdoor sensor
CO1 > F02 - 1
Cooling control
0
CO1, 2 > F04 - 1
Four-point characteristic
0
CO1, 2 > F11 - 1
Parameters
WE
Parameters: value range
Outdoor temperature
Point 1
Point 2
Point 3
Point 4
5.0 °C
15.0 °C
25.0 °C
30.0 °C
PA1, 2 > P05:
–50,0 bis 50,0 °C
Flow temperature
Point 1
Point 2
Point 3
Point 4
20.0 °C
15.0 °C
10.0 °C
5.0 °C
PA1, 2 > P05: –5.0 to 150.0 °C
Reduced flow temperature
Point 1
Point 2
Point 3
Point 4
30.0 °C
25.0 °C
20.0 °C
15.0 °C
PA1, 2 > P05: –5.0 to 150.0 °C
Base point for return flow temperature
65.0 °C
PA1, 2 > P13: 5.0 to 90.0 °C
The limiting factors 'KP' of the return flow sensor (CO1, 2 > F03) functions apply during
cooling control as well.
Cooling control without outdoor sensor
When the cooling control function is activated in a control circuit without outdoor sensor, only
the adjustment limits for the day and night set points at the rotary switch as well as the 'Base
point for return flow temperature' can be adjusted in PA1 and/or PA2.
Functions
WE
Configuration
Outdoor sensor
CO1 > F02 - 0
Cooling control
0
CO1, 2 > F04 - 1
Parameters
WE
Switch position: value range
Note