EQJW146F002 EN
145
Appendix
P
Display reading
Parameter: Value range (default setting)
14
Max. return flow temperature:
5.0 to 90.0 °C (65.0 °C)
15
Set point boost (pre-control circuit):
0.0 to 50.0 °C (5.0 °C)
16
Minimum set point to charge buffer tank:
OT to 90.0 °C (AT)
17
Stop charging of the buffer tank:
OT to 90.0 °C (AT)
18
Charging temperature boost:
0.0 to 50.0 °C (6.0 °C)
19
Lag time of charging pump
0.0 to 10.0 (1.0)
PA2: Heating circuit HC2
P
Display reading
Parameter: Value range (default setting)
01
Flow gradient:
0.2 to 3.2 (1.8)
0.2 to 1.0 (1.0) with CO2 > F05 - 1
02
Level (parallel shift):
–30.0 to 30.0 °C (0.0 °C)
03
Flow set point (day) (only with CO2 > F02 - 0 and CO2 >
F09 - 1):
–5.0 to 150.0 °C (50.0 °C)
04
Flow set point (night) (only with CO2 > F02 - 0 and CO2 >
F09 - 1):
–5.0 to 150.0 °C (30.0 °C)