24
EQJW146F002 EN
Operation
Public holidays that are not assigned to a specific date should be deleted by the end of the
year so that they are not carried on into the following year.
2.6.3
Vacations
The system runs constantly in reduced mode during vacation periods. A maximum of ten va-
cation periods can be entered. Each vacation period can be separately assigned to the heat-
ing circuits HC1, HC2 and DHW circuit or to all control circuits.
Parameters
WE
Value range
Vacation period
--.-- - --.--
01.01 to 31.12
Turn the rotary switch to (special times-of-use). The party
timer for the first control circuit is now selected.
q
Select 'Vacations'.
¼
Start the vacations setting. The first vacations setting is
now selected. --.-- - --.--.is displayed if no vacations (de-
fault setting) have been programmed.
q
Select --.-- - --.--, if applicable.
q
Activate editing mode for vacations.
The start date can now be edited (inverted reading).
q
Set the start date.
q
Confirm the start date.
The end date can now be edited.
q
Set the end date.
Note