EQJW146F002 EN
Start-up
¼
Select CO5 configuration level.
¼
Open CO5 configuration level.
¼
Select F20 function block.
¼
Activate editing mode for F20 function block.
q
Select F20 configuration.
¼
Activate editing mode for configuration.
The currently active configuration '0' or '1' is shown in-
verted on the display.
q
Activate function block ('1').
¼
Confirm activation.
¼
Select the temperature that you want to calibrate.
¼
Open calibration.
The temperature is shown inverted on the display.
¼
Correct measured value.
Read the actual temperature directly from the thermome-
ter at the point of measurement and enter this value as
the reference temperature.
¼
Confirm corrected measured value.
¼
Proceed in the same manner to calibrate further sensors.
Exit configuration level:
q
Select 'Back'.
q
Exit configuration level.
Turn the rotary switch back to (operating level).