26
EQJW146F002 EN
Operation
2.7 Entering day and night set points
The desired room temperature for the day and night set points can be programmed.
Switch position
Parameters
WE
Value range
HC1 room temperature
20.0 °C
0.0 to 40.0 °C
HC2 room temperature
20.0 °C
0.0 to 40.0 °C
DHW temperature
60.0 °C
Min. to max. DHW temperature
HC1 OT deactivation value
22.0 °C
0.0 to 50.0 °C
HC2 OT deactivation value
22.0 °C
0.0 to 50.0 °C
Switch position
Parameters
WE
Value range
HC1 room temperature
15,0 °C
0.0 to 40.0 °C
HC2 room temperature
15,0 °C
0.0 to 40.0 °C
DHW temperature
40.0 °C
Min. to max. DHW temperature
HC1 OT deactivation value
15,0 °C
–50.0 to 50.0 °C
HC2 OT deactivation value
15,0 °C
–50.0 to 50.0 °C
Turn the rotary switch to (day set point) or (night set
point).
The day or night set points are listed on the display.
Î
Only those day and night set points are available for se-
lection which can be controlled by the selected system.
The deactivation values are located in a separate menu (de-
activation values) for systems with three control circuits.
q
Select the set point.
Note