Appendix
P
Display reading
Parameter: Value range (default setting)
05
Four-point characteristic
Outdoor temperature:
–50.0 to 50.0 °C (–15.0 °C, –5.0 °C, 5.0 °C, 15.0 °C)
with CO1 > F04 -1: (5 °C, 15 °C, 25 °C, 30 °C)
Flow temperature:
–5.0 to 150.0 °C (70.0 °C, 55.0 °C, 40.0 °C, 25.0 °C)
with CO1 > F04 -1: (20 °C, 15 °C, 10 °C, 5 °C)
Reduced flow temperature:
–5.0 to 150.0 °C (60.0 °C, 40.0 °C, 20.0 °C, 20.0 °C)
with CO1 > F04 -1: (30 °C, 25 °C, 20 °C, 15 °C)
Return flow temperature:
5.0 to 90.0 °C (65.0 °C, 65.0 °C, 65.0 °C, 65.0 °C)
Flow rate:
0.01 to 650 m³/h (0.00 m³/h, 0.00 m³/h, 0.00 m³/h, 0.00 m³/h)
06
Min. flow temperature:
–5.0 to 150.0 °C (20.0 °C)
07
Max. flow temperature:
5.0 to 150.0 °C (90.0 °C)
5.0 to 50.0 °C (50.0 °C) with CO1 > F05 - 1
09
Outdoor temperature for continuous day mode:
–50.0 to 5.0 °C (–15 °C)
10
Minimum flow temperature set point HC for binary demand
processing:
5.0 to 150.0 °C (40.0 °C)
11
Return flow gradient:
0.2 to 3.2 (1.2)
12
Return flow level:
–30.0 to 30.0 °C (0.0 °C)
13
Base point for return flow temperature:
5.0 to 90.0 °C (65.0 °C)