EQJW146F002 EN
147
Appendix
PA4: Domestic hot water heating (DHW)
P
Display reading
Parameter: Value range (default setting)
01
Min. adjustable DHW set point:
5.0 to 90.0 °C (40.0 °C)
02
Max. adjustable DHW set point:
5.0 to 90.0 °C (90.0 °C)
03
Hysteresis:
1.0 to 30.0 °C (5.0 °C)
04
Charging temperature boost:
0.0 to 50.0 °C (10.0 °C)
05
Max. charging temperature (only with CO4 > F05 - 1):
20.0 to 150.0 °C (80.0 °C)
07
Max. return flow temperature:
20.0 to 90.0 °C (65.0 °C)
10
Solar circuit pump ON:
1.0 to 30.0 °C (10.0 °C)
11
Solar circuit pump OFF:
0.0 to 30.0 °C (3.0 °C)