ACU-100 SATEL
5
2.2 F
UNCTIONS OF
DIP-
SWITCHES
DIP-switch number
Controller function
1 2 3 4 5 6 7 8
Wireless device module for all control panels
I
1
I
2
I
3
x P 0 0 0
Expander for CA-10 with 1 keypad (6 zones)
A B C D P 1 0 0
Expander for CA-10 with 2 keypads (4 zones)
A B C D P 0 1 0
Expander for CA-10 with 3 keypads– (2 zones)
A B C D P 1 1 0
Addressable zone expander for CA-64
A
1
A
2
A
3
A
4
A
5
P 0 1
Wireless device expander for INTEGRA control panels
A
1
A
2
A
3
A
4
A
5
x 1 1
Table 1. The way of using DIP-switches for controller configuration.
0
– DIP-switch in OFF position
1
– DIP-switch in ON position
P
– selection of controller programming mode:
−
DIP-switch in OFF position – through RS-232 port (D
LOAD
10 program)
−
DIP-switch in ON position – by means of LCD keypad
I
1
,
I
2
,
I
3
– DIP-switches for setting the number of ACX-100 modules connected to the
computer. To determine this number, tot up the values set on individual DIP-switches as
per Table 2.
DIP-switch number
1
2
3
Numerical value
(for switch in ON position)
1 2 4
Table 2.
The controller accepts up to 5 input/output expansion modules, hence if a higher value
is set on the DIP-switches, it will be also recognized as 5.
A
,
B
,
C
,
D
– DIP-switches for setting the controller address in the same way as with the CA-
10 zone expanders. When in the ON position, the switch value is 1.
A
1
,
A
2
,
A
3
,
A
4
,
A
5
- DIP-switches for setting the controller address. In order to determine the
controller address, add up the values set on individual DIP-switches as per Table 3.
DIP-switch
number
1 2 3 4 5
Numerical value
(for switch in ON position)
1 2 4 8 16
Table 3.
x
- unused DIP-switch
2.3 C
ONTROL INPUTS
The ACU-100 PCB incorporates 4 control inputs. These inputs make it possible to control
operation of wireless equipment (detectors, sirens). How the device will respond to activation
of the input (shorting to common ground / opening connection) depends on the type of the
device controlled by the input (e.g. the detectors will change to active status, the sirens will
trigger alarm signal, the 230V AC wireless controllers will turn on electrical equipment
connected to their sockets, etc.). The control inputs are disabled when the controller operates
with the INTEGRA control panels.
The controller inputs can be programmed as NO (normally open) or NC (normally shorted to
ground).