Troubleshooting
38
2/3
UPS Status
LCD Indication
LED Status
Countermeasure
-STANDBY-
Green INPUT: On
Was
on the LCD panel or
on the UPS Unit control panel pressed
accidentally and set to “OFF”?
Perform the correct procedure to set it to “ON.”
Byp Fuse Error
Red ALARM: On
Red WARNING:
On
Has
MAIN MCCB
tripped?
The breaker may have tripped by an overload or short circuit.
Check the load capacity and whether there is a short circuit.
If the load capacity is high, reduce the number of load devices connected to
the terminal block of the UPS. See “§9.3 Resetting the Main Breaker.”
Are the unit-to-unit output cables connected properly?
See “§6.3.1 Wiring Between UPS Units,” and connect the cables properly.
Remote OFF
Green INPUT: On
Is the remote OFF signal being input? See “§5.4 External Interface,” and
check whether the external control terminal is connected properly.
Power from the terminal
block of the UPS stopped
during operation.
EPO ON
Green INPUT: On
Is the EPO signal being input? See “§5.4 External Interface,” and check
whether the external control terminal is connected properly.
An overload state occurs
even though the connected
load devices do not exceed
the UPS rated capacity.
Over load
-
Are the unit-to-unit output cables connected to the back of the UPS Units
properly?
If there is a UPS Unit that is not connected, the output capacity will be
reduced by an amount equivalent to the capacity of the unit. See Ҥ6.3.1
Wiring Between UPS Units,” and connect it properly.
Is
MAINTENANCE BYPASS
set to “ON”?
If it is set to “ON,” set it to “OFF.” Set the switch to “OFF” for UPS
operation.
Power from the terminal
block of the UPS stopped
during a power outage.
-
-
Have the batteries deteriorated?
Check the time to replace the batteries.
The battery service life will vary depending on the ambient temperature.
Early battery replacement is recommended.
Did a power outage occur within the last 12 hours? The remaining capacity
of the batteries may be low. Sufficiently charge the UPS.
The buzzer sounded.
-
-
The buzzer sounds when a state change, warning, or error occurs in the
UPS.
See “§10. When A Buzzer Sounds.”
The buzzer does not sound.
-
-
Is “Buzzer” in the LCD panel setting menu set to “SILENT” (stopped)?
See “§3.8 Setting Buzzer Condition” in the LCD Panel Operating Manual
and check the setting value.
Nothing is displayed on the
LCD panel.
-
-
Are the UPS Unit and LCD panel connected properly with the connection
cable?
See “§6.2 Installing the Battery Packs and Attaching the Front Panel.”
Cannot operate the LCD
panel.
-
-
Are the UPS Unit and LCD panel connected properly with the connection
cable?
See “§6.2 Installing the Battery Packs and Attaching the Front Panel.”
The LEDs on the UPS Unit
control panel do not turn
on.
- All:
Off
Is
MAIN MCCB
set to “ON”?
See “§8.1 Starting the UPS” and check the correct operating procedure.
The LEDs on the UPS Unit
control panel of one UPS
Unit do not turn on.
-
All LEDs on one
UPS Unit are
off.
Is
MAIN MCCB
of the UPS Unit for which the LEDs do not turn on set to
ON?
See “§8.1 Starting the UPS” and check the correct operating procedure.
Cannot operate the UPS
Unit control panel.
- Red
ALARM:
On
The UPS has malfunctioned. Contact your sales representative or SANYO
DENKI.
The battery power supply
continues.
The power supply switches
to battery power supply
frequently.
Input Error
Input Freq Err
Input Vol Hi
Input Vol Low
Green BACKUP:
On
Is
MAIN MCCB
set to “ON”? If it is set to “OFF,” set it to “ON.” (If MAIN
MCCB is set to “OFF” during normal operation, the operation will become
the same as for a utility power supply failure and the power supply will
switch to battery power.)
Check that the input voltage and input frequency are within rated ranges.
See “§12.4 Specifications.”
Cannot perform a battery
test.
- -
A battery test cannot be performed when:
①
The inverter is stopped.
②
The bypass power supply is active.
③
The battery operation is being performed.
④
A shutdown is being performed by, for example, a remote operation.
⑤
The UPS has malfunctioned.
⑥
During asynchronous operation.
⑦
The frequency setting is fixed to “50 Hz” or “60 Hz.”