Part Names
14
No.
Name
Function
③
SIGNAL I/F
Contact signal
interface connector
Outputs status information of the UPS such as a power outage or voltage drop.
External Transmission Signals and Shutdown Input Signals
Signal Name
Description
Pin No.
and
Status when
Operating
AC input error
This signal is output when there is a power outage or
voltage error of the utility power supply.
1-8: ON
2-8: OFF
Battery voltage
drop
This signal is output when the battery voltage drops to or
below the specified value (approx. 178 V).
3-11: ON
AC output
This signal is output when AC output is being supplied to
a load device.
4-7: ON
15-7: OFF
Inverter output
This signal is output when inverter output is being
supplied to a load device.
14-8: ON
Bypass output
This signal is output when the utility power supply is
being
supplied from the bypass circuit.
5-12: ON
Ou
tp
u
t Sig
n
al
Device error
This signal is output when a UPS error occurs.
6-13: ON
Inp
u
t S
ig
n
al
UPS shutdown
The UPS is shut down as a result of receiving 5 V DC
(pulse signal of at least 4 sec.) during battery operation
when there is a power outage. Current flows at
approximately 5 mA when the power is on.
This is enabled when the interface is set to Standalone .
For the setting procedure, see
“
§3.5 Setting PC Interface”
in the LCD Panel Operating Manual.
9-10
External Transmission Signals and Electrical Characteristics
Interface: Relay non-voltage contact signal
Contact rating: 50 V DC, 0.1 A
Terminal Names External Appearance
④
Switches for
independent contact
signals
Setting these switches to “OFF” makes each contact of the external transmission signals
independent.
Refer to contact interface connector
③
, and set to “ON” or “OFF” according to how the UPS
will be used by the customer. The switches are all set to “ON” at the time of shipment from
the factory.
External Appearance
When all of
1 to 4 are in
the “ON” state.
Set them to "OFF" when using each contact signal as an
independent circuit.
Set them to "ON" when using each contact signal as a common
COM circuit.
When connecting an inductive/capacitive load, make sure the contact rating is not exceeded.
Note
D-sub 15-pin Female
①
②
③
④
⑤
⑥
⑦
⑧
Fixing Screw M3
⑨
⑩
⑪
⑫
⑬
⑭
⑮
AC input error
2
S1 to S4 : Switches for independent contact signals (see
④
)
3
12
4
7
14
5
COM
Battery voltage drop
AC output
COM
Inverter output
Bypass output
Device error
UPS shutdown
15
1
8
11
6
13
9
10
S1
S2
S3
S41
COM
COM
COM