S&C Instruction Sheet 681-530
7
Shipping and Handling
Examine the shipment for external evidence of damage as soon after receipt as possible,
preferably before the carrier departs. Check the bill of lading to make sure the listed
shipping packages are present.
If there is visible loss and/or damage:
1. Notify the delivering carrier immediately.
2. Ask for a carrier inspection.
3. Note condition of shipment on all copies of the delivery receipt.
4. File a claim with the carrier.
If concealed damaged is discovered:
1. Notify the delivering carrier within 15 days of receipt of shipment.
2. Ask for a carrier inspection.
3. File a claim with the carrier.
Notify S&C Electric Company in all instances of loss and/or damage.
Inspection
The overcurrent control for your S&C Vista Underground Distribution System is housed
in an enclosure mounted on the operation side of the switchgear. For UnderCover™ Style
and Wet-Vault Mounted-Style Vista Underground Distribution Switchgear, the enclosure
is fully submersible. The overcurrent control electronics module is removable for bench
programming.
Packing
DANGER
Never disconnect the current transformer secondary circuits without de-energizing
the switchgear . Hazardous voltage is present and will shock, burn, or cause death .
NOTICE
Handle the overcurrent control’s electronics module carefully when removing it
from the enclosure . DO NOT drop the overcurrent control or subject the control to
moisture or any undue stress . After the overcurrent control has been configured,
return it to the enclosure on the Vista Underground Distribution Switchgear .
Handling