S&C Instruction Sheet 681-530
29
Programming the Control Settings
At the factory, S&C Electric Company renames the fault interrupter to match its way
designation depending on the switchgear confi guration. (i.e. if the fault interrupter is
on Way 4, the fault interrupter will be named “Way 4.”)
The fault interrupter IDs can be changed to match the application.
To change the names:
STEP 1.
Select the appropriate interrupter fi eld and type in the desired name. See
Figure 25. Interrupter names can be up to 16 characters excluding special
characters such as “/, &, #, $, and :”. This name will be propagated throughout
the
Overcurrent Control
settings and will change the name in the
Selection
menu, Event logs,
Trip test
screen, and
Status
screen.
STEP 2.
Click on the
Save
button. A message that the setting has been saved will display.
The global settings are programmed at the factory to match the Vista switchgear model.
Recheck all settings to make sure they are accurate before energizing the switchgear. If
Single-Pole Trip/Three-Phase Lockout
settings are required, they should be selected
under the
Trip Mode
menu. If the switchgear is applied at 50 Hz, select 50 Hz under the
Global Settings
menu.
NOTICE
If problems are encountered trying to change the Global Settings while running
Microsoft Internet Explorer in compatibility mode, disable compatibility mode or try
again using a different web browser .
NOTICE
The overcurrent control will logout the user after five minutes of inactivity . Any
settings not saved before the inactivity logout will be lost .
Changing the
Interrupter ID
Changing the Global
Settings
Figure 25. The Change Interrupter ID menu.