Overcurrent Control Settings
The Vista Overcurrent Control can be programmed to provide a wide variety of settings
combinations. Listed below are the setting ranges that are available to the overcurrent
control.
Table 12. IEC Curves
Time Overcurrent Phase Protection
Inverse Segment
Standard Inverse (C1)
Very Inverse (C2)
Extremely Inverse (C3)
Long-Time Inverse
(C4)
Short-Time Inverse
(C5)
Continuous Current
600
900
Short Circuit, RMS Sym.
Short Circuit, RMS Sym.
12.5 and 16 kA
25 kA
12.5 and 16 kA
25 kA
Minimum Trip Current, A 14 to 12500 in steps
of 0 .01
14 to 13200 in
steps of 0 .01
28 to 12500 in steps
of 0 .01
28 to 13200
in steps of
0 .01
Low-Current Cutoff, A
●
14 to 12500 in steps
of 0 .01
14 to 13200 in
steps of 0 .01
28 to 12500 in steps
of 0 .01
28 to 13200
in steps of
0 .01
Time Multiplier
0 .05 to 1 in steps of 0 .01
Time Adder, s
0 to 1000 in steps of 0 .01
Definite-Time Phase Protection Element #1
Definite-Time Current,
A
■
14 to 12500 in steps
of 0 .01
14 to 13200 in
steps of 0 .01
28 to 12500 in steps
of 0 .01
28 to 13200
in steps of
0 .01
Definite-Time Time, s
0 – 1000 in steps of 0 .001
Definite-Time Phase Protection Element #2
Definite-Time Current,
A
▲
14 to 12500 in steps
of 0 .01
14 to 13200 in
steps of 0 .01
28 to 12500 in steps
of 0 .01
28 to 13200
in steps of
0 .01
Definite-Time Time, s
◆
0 – 1000 in steps of 0 .001
Reset Time Parameters
Reset Type
TIMED
Reset Time, s
▼
0 to 1000 in steps of 0 .001
●
Low-current cutoff must be equal to or greater than the minimum trip current .
■
Definite time current must be greater than or equal to low-current cutoff and/or the minimum trip current .
▲
Definite Time Current 2 should be greater than or equal to Definite Time Current 1 .
◆
Time should be less than Definite-Time 1 .
▼
Accumulated value will reset to zero after the reset time has elapsed .