Code 30
✴✴
: User’s options for domestic hot water(DHW) tank heating
3011 : Application of DHW tank in user’s system
302
✴
: Heat pump variables for tank temp. control and combination with booster heater
303
✴
: Booster heater variables for combination with heat pump
304
✴
: Periodical disinfection heating of water tank
305
✴
: Off timer for power DHW mode by Forced DHW of wired remote controller
3061 : Combination of external field solar panel for with heat pump for DHW heating
307
✴
: Default direction of the DHW valve or Zone #1, #2 valve
When the 3way valve is applied to DHW Valve terminal block instead of 2way valve, default direction is Space
Heating (Room)
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub Code
Default
Min
Max
Step
Unit
DHW Code
30
✴✴
Domestic Hot Water Tank
Application
✴✴
11
0(No)
0
1(Yes)
-
-
Heat Pump
Max Temp
✴✴
21
50
45
50
1
˚C
Stop
✴✴
22
2
2
10
1
˚C
Start
✴✴
23
5
5
20
1
˚C
Min. Space heating
operation time
✴✴
24
5
1
20
1
min
Max. DHW operation time
✴✴
25
30
5
95
5
min
Max. Space heating
operation time
✴✴
26
3
0.5
10
0.5
hour
Booster Heater
Application
✴✴
31
1(On)
0(Off)
1
-
-
Delay Time
✴✴
32
20
20
95
5
min
Overshoot
✴✴
33
0
0
4
1
˚C
Compensation Temp
✴✴
34
10
0
20
1
˚C
Disinfection
Application
✴✴
41
1(On)
0(Off)
1
-
-
Interval
✴✴
42
Fri(5)
Sun(0)
All(7)
1
day
Start Time
✴✴
43
23
0
23
1
o'clock
Target Temp
✴✴
44
70
40
70
5
˚C
Duration
✴✴
45
10
5
60
5
min
Forced DHW operation
Timer OFF Function
✴✴
51
0(Off)
0
1(On)
-
-
Timer Duration
✴✴
52
6
3
30
1
(x10)
min
Solar Panel/DHW Thermostat
H/P Combination
✴✴
61
0
0
2
-
-
Direction of DHW valve
DHW Tank
✴✴
71
0(Room)
0
1(Tank)
-
-