ENGLISH-39
03
AD
VANCED
OPER
ATION
•
Code 5042
[D-00]
Compressor
Back up heater
Booster heater
0 (Default)
Permitted
Forced off
Permitted
1
Permitted
Forced off
Forced off
2
Forced off
Forced off
Permitted
Remote Controller Setting Range : Code 10
✴✴
Field Setting Value
Main Menu & Code
Sub Menu Function
Description
Sub Code Default Min
Max
Step
Unit
Remote Controller
Setting Range Code
10
✴✴
Water Out Temp for Cooling
Max
✴✴
11
25
18
25
1
˚C
Min
✴✴
12
16
5
18
1
˚C
Room Temp for Cooling
Max
✴✴
21
30
28
30
1
˚C
Min
✴✴
22
18
18
28
1
˚C
Water Out Temp for Heating
Max
✴✴
31
55
37
55
1
˚C
Min
✴✴
32
25
15
37
1
˚C
Room Temp for heating
Max
✴✴
41
30
18
30
1
˚C
Min
✴✴
42
16
16
18
1
˚C
DHW Tank Temp
Max
✴✴
51
50
50
70
1
˚C
Min
✴✴
52
40
30
40
1
˚C
Space Cooling
•
Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC),
Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
- With this default FSV settings, user can change the target water outlet temperature within the range of 5 ~ 25ºC for
cooling
•
Target room temperature : Upper limit(#1021, Default 30ºC), Lower limit(#1022, Default 18ºC)
- With this default FSV settings, user can change the target room temperature within the range of 18 ~ 30ºC for cooling.
Space Heating
•
Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC),
Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
- With this default FSV settings, user can change the target water outlet temperature within the range of 25 ~ 55ºC for
heating.
•
Target room temperature : Upper limit(#1041, Default 30ºC), Lower limit(#1042, Default 16ºC)
- With this default FSV settings, user can change the target room temperature within the range of 16 ~ 30ºC for heating.
DHW Heating
•
Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 70ºC),
Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
- With this default FSV settings, user can change the target tank temperature within the range of 40 ~ 50ºC for DHW
heating.
•
The FSV #3011 in the wired remote controller should be set to “1(Yes)” to use DHW function.
NOTE