ENGLISH-40
Field setting mode
Water Law & Room Thermostat : Code 20
✴✴
Ts
Ta
H1
H2
C1
C2
#2021/2031
#2022/2032
#2061/2071
#2062/2072
#2011
#2012
#2051
#2052
Ts : Target Temp.
Ta : Ambient Temp.
Cooling WL
Heating WL
Floor FCU
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub Code Default Min
Max
Step
Unit
Water Law Code
20
✴✴
Outdoor Temp for Water Law (Heating)
H1
✴✴
11
-10
-20
5
1
˚C
H2
✴✴
12
15
10
20
1
˚C
Water Out Temp for WL1 Heating (WL1-Floor)
H1
✴✴
21
40
17
55
1
˚C
H2
✴✴
22
25
17
55
1
˚C
Water Out Temp for WL2 Heating (WL2-Fan
Coil Unit)
H1
✴✴
31
50
17
55
1
˚C
H2
✴✴
32
35
17
55
1
˚C
Heating Water Law for Auto Mode
WL Type
✴✴
41 1(WL1)
1
2
-
-
Outdoor Temp for Water Law (Cooling)
C1
✴✴
51
30
25
35
1
˚C
C2
✴✴
52
40
35
45
1
˚C
Water Out Temp for WL1 Cooling (WL1-Floor)
C1
✴✴
61
25
5
25
1
˚C
C2
✴✴
62
18
5
25
1
˚C
Water Out Temp for WL2 Cooling (WL2-Fan
Coil Unit)
C1
✴✴
71
18
5
25
1
˚C
C2
✴✴
72
5
5
25
1
˚C
Cooling Water Law for Auto Mode
WL Type
✴✴
81 1(WL1)
1
2
-
-
External Thermostat Application
#1(Floor)
✴✴
91
0(No)
0
1(Yes)
-
-
#2(FCU)
✴✴
92
0(No)
0
1(Yes)
-
-
Water Law for Heating
•
Outdoor air temperature range : Lower limit H1(#2011, Default -10˚C, Range : -20 ~ 5˚C),
Upper limit H2(#2012, Default 15˚C, Range : 10 ~ 20˚C)
- With this default settings, the water outlet temperature by heating water law can be changed within the outdoor
temperature range of -10 ~ 15˚C.
•
Water out temperature range for floor/FCU applications respectively :
Upper limit H1(#2021/2031, Default 40/50˚C, Range : 17 ~ 55˚C),
Lower limit H2(#2022/2032, Default 25/35˚C, Range : 17 ~ 55˚C)
- With this default settings, the water outlet temperature by heating water law can be changed within the range of 25/35
~ 40/50˚C.
•
Type of water law for according to heating devices(floor/FCU) : #2041(Default “1”(WL1 for floor)), “2”(WL2 for FCU or
radiator)