Field setting mode
Field Setting Value (FSV) Table
•
Reset the power after changing the Field Setting Value.
NOTE
•
Code 10
✴✴
: Upper and lower temperature limits of each operation mode of wired remote controller Heating(Water Out,
Room), Cooling(Water Out, Room), DHW(Tank)
•
Code 20
✴✴
: Water law design and external room thermostat Heating(2 WL’s for floor & FCU), Cooling(2 WL’s for floor &
FCU), WL & Thermostat types
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub Code
Default
Min
Max
Step
Unit
Remote
Controller
Setting Range
Code 10
✴✴
Water Out Temp for Cooling
Max
✴✴
11
25
18
25
1
˚C
Min
✴✴
12
16
5
18
1
˚C
Room Temp for Cooling
Max
✴✴
21
30
28
30
1
˚C
Min
✴✴
22
18
18
28
1
˚C
Water Out Temp for Heating
Max
✴✴
31
55
37
55
1
˚C
Min
✴✴
32
25
15
37
1
˚C
Room Temp for heating
Max
✴✴
41
30
18
30
1
˚C
Min
✴✴
42
16
16
18
1
˚C
DHW Tank Temp
Max
✴✴
51
50
50
70
1
˚C
Min
✴✴
52
40
30
40
1
˚C
Water Law
Code 20
✴✴
Outdoor Temp for Water Law (Heating)
H1
✴✴
11
-10
-20
5
1
˚C
H2
✴✴
12
15
10
20
1
˚C
Water Out Temp for WL1 Heating
(WL1-Floor)
H1
✴✴
21
40
17
55
1
˚C
H2
✴✴
22
25
17
55
1
˚C
Water Out Temp for WL2 Heating (WL2-
Fan Coil Unit)
H1
✴✴
31
50
17
55
1
˚C
H2
✴✴
32
35
17
55
1
˚C
Heating Water Law for Auto Mode
WL Type
✴✴
41
1(WL1)
1
2
-
-
Outdoor Temp for Water Law (Cooling)
C1
✴✴
51
30
25
35
1
˚C
C2
✴✴
52
40
35
45
1
˚C
Water Out Temp for WL1 Cooling
(WL1-Floor)
C1
✴✴
61
25
5
25
1
˚C
C2
✴✴
62
18
5
25
1
˚C
Water Out Temp for WL2 Cooling (WL2-
Fan Coil Unit)
C1
✴✴
71
18
5
25
1
˚C
C2
✴✴
72
5
5
25
1
˚C
Cooling Water Law for Auto Mode
WL Type
✴✴
81
1(WL1)
1
2
-
-
External Thermostat Application
#1(Floor)
✴✴
91
0(No)
0
1(Yes)
-
-
#2(FCU)
✴✴
92
0(No)
0
1(Yes)
-
-