ENGLISH-38
Field setting mode
•
Code 40
✴✴
: User’s options for heating devices including internal backup heater and external boiler
401
✴
: Space/DHW heating priority and control variables
402
✴
: Backup/Booster heater priority and control variables
403
✴
: Additional backup boiler operating variables
•
Code 50
✴✴
: User’s options for extra functions
501
✴
: New target temperatures of each mode by “Outgoing” hot key of remote controller
5021 : Temperature difference between before & after values in “Economic” DHW mode
504
✴
: Power Peak control for Smart Grid
Field Setting Value
Main Menu &
Code
Sub Menu Function
Description
Sub Code Default
Min
Max
Step Unit
Heating Code
40
✴✴
Heat Pump
Heating/DHW Priority
✴✴
11
0(DHW)
0
1(Heating)
-
-
Outdoor Temp for Priority
✴✴
12
0
-15
20
1
˚C
Heating Off
✴✴
13
35
14
35
1
˚C
Overshoot
✴✴
14
2
1
4
1
˚C
Backup Heater
Application
✴✴
21
0(No)
0
1(Yes)
-
-
BUH/BSH Priority
✴✴
22
0(Both)
0
2(BSH)
1
-
Cold weather compensation
✴✴
23
1(Yes)
0(No)
1
-
-
Threshold Temp
✴✴
24
0
-15
35
1
˚C
Defrost Backup Temp.
✴✴
25
15
10
55
5
˚C
Backup Boiler
Application
✴✴
31
0(No)
0
1(Yes)
-
-
Boiler Priority
✴✴
32
0(No)
0
1(Yes)
-
-
Threshold Temp
✴✴
33
-15
-20
5
1
˚C
Mixing valve
Application
✴✴
41
0(No)
0
1(Yes)
-
-
Target ΔT(Heating)
✴✴
42
10
5
15
1
˚C
Target ΔT(Cooling)
✴✴
43
10
5
15
1
˚C
Control factor
✴✴
44
2
1
5
1
-
Control interval
✴✴
45
2
1
30
1
min
Running Time
✴✴
46
9
6
24
3
(x10)
sec
Inverter Pump
Application
✴✴
51
1(Yes)
0
1(Yes)
-
-
Target ΔT
✴✴
52
5
2
8
1
˚C
Control factor
✴✴
53
2
1
3
1
-
Others Code
50
✴✴
Outing
Water Out Temp for Cooling
✴✴
11
25
5
25
1
˚C
Room Temp for Cooling
✴✴
12
30
18
30
1
˚C
Water Out Temp for Heating
✴✴
13
15
15
55
1
˚C
Room Temp for Heating
✴✴
14
16
16
30
1
˚C
Auto Cooling WL1 Temp
✴✴
15
25
5
25
1
˚C
Auto Cooling WL2 Temp
✴✴
16
25
5
25
1
˚C
Auto Heating WL1 Temp
✴✴
17
15
15
55
1
˚C
Auto Heating WL2 Temp
✴✴
18
15
15
55
1
˚C
Target Tank Temp
✴✴
19
30
30
70
1
˚C
DHW Saving Mode
Temp Difference
✴✴
21
5
0
40
1
˚C
Power Peak Control
Application
✴✴
41
0(No)
0
1(Yes)
-
-
Select forced off parts
✴✴
42
0(All)
0
2
1
-
Using input voltage
✴✴
43
1(High) 0(Low)
1
-
-
Frequency Ratio Control
✴✴
51
0(No)
0
1(Yes)
-
-