Installation and operating instructions Ixens, Ixens Bloc
127
12
Spare parts
Spare parts may be ordered via a local specialist and/or Samson cus-
tomer service.
When ordering spare parts, make sure to state all the information
given on the pump and drive rating plates (for the pump rating plate,
see Fig. 11, Item 1, for the drive rating plate, see Fig. 12, Item 3)
.
This
helps prevent return queries and incorrect orders.
CAUTION! Risk of property damage!
Trouble-free pump operation can only be guaranteed when origi-
nal spare parts are used.
• Only use original Salmson spare parts.
• Each component is identified in the table below.
• Information to be provided when ordering spare parts:
• Spare part number
• Name/description of the spare part
• All data on the pump and drive rating plates
NOTE:
For a list of original spare parts, see the Salmson spare parts docu-
mentation (www.salmson.com). The item numbers on the exploded
view drawing (Fig. 7) are intended as orientation and to provide a list
of the pump components (see list “Tab. 2: Arrangement of the main
components” on page 76). These item numbers are not to be used to
order spare parts.
13
Factory settings
For the factory settings, see Tab. 13 below.
Menu
no.
Designation
Factory-configured values
1.0.0.0 Setpoints
• Controller:
approx. 60 % of n
max
pump
•
Δ
p-c:
approx. 50 % of H
max
pump
•
Δ
p-v:
approx. 50 % of H
max
pump
2.0.0.0 Control mode
Δ
p-c activated
3.0.0.0
Δ
p-v gradient
Lowest value
2.3.3.0 Pump
ON
4.3.1.0 Base-load pump
MA
5.1.1.0 Operating mode
Main/standby operation
5.1.3.2 Internal/external pump
cycling
Internal
5.1.3.3 Pump cycling time interval
24 h
5.1.4.0 Pump enabled/disabled
Enabled
5.1.5.0 SSM
Collective fault signal
5.1.6.0 SBM
Collective run signal
5.1.7.0 External off
Collective external off
5.3.2.0 IN1 (value range)
0–10 V active
5.4.1.0 IN2 active/inactive
OFF
5.4.2.0 IN2 (value range)
0–10 V
5.5.0.0 PID parameter
See chapter 9.4 “Setting the con-
trol mode” on page 110
5.6.1.0 HV/AC
HV
5.6.2.0 Emergency operation speed
approx. 60 % of n
max
pump
5.6.3.0 Auto reset time
300 s
5.7.1.0 Display orientation
Display on original orientation
5.7.2.0 Pressure value correction
Active
Summary of Contents for IXENS
Page 2: ......
Page 3: ......
Page 8: ...Fig 7 Ixens 13 20 22 21 15 16 17 18 19 14 13 12 11 10 9 8 7 4 3 2 1 6 5 20b 20a ...
Page 75: ...Français Notice de montage et de mise en service Ixens Ixens Bloc 67 ...
Page 137: ...English Installation and operating instructions Ixens Ixens Bloc 129 ...
Page 203: ...Italiano Istruzioni di montaggio uso e manutenzione Ixens Ixens Bloc 195 ...
Page 335: ......