English
Installation and operating instructions Ixens, Ixens Bloc
101
• Set DIP switch 1 to the ON position.
Service mode is activated. The symbol shown here flashes on the sta-
tus page.
The sub-elements of menu 5.0.0.0 switch from the “Information”
element type to the “Selection/setting” element type, and the stand-
ard “access disable” symbol (see symbol) is hidden for the respective
elements (except for <5.3.1.0>).
The values and settings for these elements can now be edited.
• To deactivate, return the switch to its starting position.
8.6.7
Activating/deactivating access
disable
In order to prevent impermissible changes to the pump settings, all
functions can be disabled.
When access is disabled, this is shown on the status page by the
default “access disable” symbol.
To activate or deactivate this, proceed as follows:
• Set DIP switch 2 to the ON position.
Menu <7.0.0.0> is displayed.
• Turn the white button to activate or deactivate the disable.
• To confirm the change, press the white button.
The current state of the disable is represented on the symbol display
by the symbols shown here.
Disable active
No changes can be made to setpoints or settings. The read access to
all menu elements remains as it was.
Disable inactive
The elements of the basic menu can be edited (menu elements
<1.0.0.0 >, <2.0.0.0> and <3.0.0.0>).
NOTE:
To edit the sub-elements of menu <5.0.0.0>, service mode must also
be activated.
• Reset DIP switch 2 to the OFF position.
The display returns to the status page.
NOTE:
Errors can be acknowledged after a waiting period despite the “access
disable” being active.
8.6.8
Activating/deactivating termination
In order to establish a definite communication connection between the
electronic modules, it is necessary to terminate both ends of the cable.
In a double pump, the modules are already prepared for double pump
communication at the factory.
To activate or deactivate this, proceed as follows:
• Set DIP switches 3 and 4 to the “ON” position.
Termination is activated.
NOTE:
Both DIP switches must always be in the same position.
• To deactivate, return the switches to the starting position.
8.7
Menu elements reference
The following table gives an overview of the available elements of all
menu levels. The menu number and the element type are designated
separately, and the function of the element is explained. If applicable,
there is information about the setting options of the individual elements.
ON
1
ON
2
ON
2
ON
2
ON
2
ON
2
Summary of Contents for IXENS
Page 2: ......
Page 3: ......
Page 8: ...Fig 7 Ixens 13 20 22 21 15 16 17 18 19 14 13 12 11 10 9 8 7 4 3 2 1 6 5 20b 20a ...
Page 75: ...Français Notice de montage et de mise en service Ixens Ixens Bloc 67 ...
Page 137: ...English Installation and operating instructions Ixens Ixens Bloc 129 ...
Page 203: ...Italiano Istruzioni di montaggio uso e manutenzione Ixens Ixens Bloc 195 ...
Page 335: ......