Parameters in the file para.ini: advanced configuration
TELSAT GPRS
91
Datei 8123AD010_11.doc
Datei gespeichert
08.03.04 17:31 von EDV/ORGA
Druckzeit 08.03.04,
17:44
Status Release
16.10 Port Allocation
Can be configured by SMS (see page 83)
Can be configured by FTP (see page 84)
Can be configured by DTMF (see page 81)
You may specify to which port incoming calls will be routed to. Incoming calls will be
routed depending on the bearer capability to distinguish between voice, data, fax and in
accordance to your configuration.
Example:
Section:
CALL_MUX
VOICE_ALERT=A
Voice calls will be routed to the
Phone port
DATA_ALERT=C
Data calls will be routed to the PC-Port
FAX_ALERT=B
Fax calls will be routed to the
Fax/Modem/Phone
A = Phone port
B = Fax/Modem/Phone port
C = PC-Port
16.11 Analogue Fax Configuration
Section:
CALL_MUX
Meaning Parameter
Permitted
Values
Factory
Setting
Fax only on Port B
(no voice)
FAX_PORT_B YES,
NO
NO
Timeout for local
fax in seconds
FAX_ACCEPT_TIMEOUT
5 to 99999
20
Maximum retries for
local fax
FAX_RETRY_MAX
0 to 99999
3
Delay between
reties in seconds
FAX_RETRY_DELAY
1 to 99999
30
Success fax after
completed MOC
FAX_SUCCESS_REPORT YES,
NO
NO
Section:
FAX
Meaning Parameter
Permitted
Values
Factory
Setting
Fax Identification
(if remote
identification is not
available, yet)
IDENT
20 chars
TELSAT GPRS
Disconnect on AC
power fail
AC_DOWN_DISCONNECT YES,NO
YES