CFIP PhoeniX C Series TDM/IP Split Mount System Technical Description and Configuration Guide
•
Rev. 1.0
•
© SAF Tehnika JSC 2013
Figure 24: Final ODU and antenna installation
ATTENTION:
Always fasten 2 latches which are against each other at the same time. Make sure that
the adapter slot and ODU waveguide slot match during the installation or while changing the
polarization.
IDU installation
CFIP Phoenix C IDU format was designed in accordance with mounting requirements for standard 19"
rack cabinet so that it occupies the least possible hight. The result is 1U height and ½ width of the
standard 19" rack position. Therefore you are able to put 2 IDUs alongside each other into 1 rack slot.
Both the devices are then connected with a special “Dual IDU mount kit” (optional accessory). The
depth of the unit's position towards 19" rack cabinet could be then changed just by shifting the
brackets holding the IDUs in their slots. Mounting the brackets for installing IDU into 19" cabinet:
–
One IDU in one slot of 19" cabinet – 1x short and 1x long bracket, both brackets are included in
standard IDU delivery (Figure 25).
Figure 25: 1x IDU in 1U 19" cabinet
–
Two IDUs in one slot of 19" cabinet – 2x short brackets, 1x Dual IDU mount kit. Use short
brackets from each IDU standard delivery, Dual IDU mount kit is an optional accessory
(Figure 26).