3050-8010
Einbau- und Betriebsanleitung
Installation and Operating instructions
Instructions de montage et de service
Regeltechnik Kornwestheim
GmbH
Max-Planck Straße 3
D-70806 Kornwestheim
T49 7154 / 13 14 - 0
T49 7154 / 13 14 - 31
Internet www.rtk.de
E-Mail [email protected]
- 48 -
11.4 Starting from automatic operation:
Once self-optimization has started the steady-state
Yopt
manipulated variable is issued. After 'Process
idling’ (PiR) is recorded, the manipulated variable interval
dYOpt
is issued and then the
procedure for finding the characteristic value is performed. The set value can be altered at any time, during
which the gradient function for adjusting the set value is inactive .
Self optimization [grad(x)=0]
Self optimization [grad(x)<0]
11.5 Starting from manual operation.
The self optimization can be started from manual operation only if the controller
is operated from the front or the interface.
On moving into manual operation, the most recently displayed manipulated variable is taken over as
the manual manipulated variable. When self-optimization starts this manipulated value is adopted and displayed as the temporary
steady-state manipulated variable. Once PiR is reached the procedure for finding the characteristic value
starts. A prerequisite for starting optimization is a sufficient set value reserve ."Process idling"
(PiR) may already be reached at the start, in which case the normal waiting period of
60s no longer applies. As in automatic operation, the set value can be adjusted at any time.
Start by raising the set value Start by lowering the control output
When self-optimization has been successfully concluded, automatic operation starts up
automatically. The characteristics of the controlled system are reserved as Tu1,Vmax1. On the basis of
these characteristics the parameters for the control response of the controller are established.
a
If self-optimization ends with an error (
Ada_F
), the steady-state manipulated variable will be displayed until
the self-optimization procedure is terminated by the user, using the system menu, the
H
key on the
front or the interface.
t
t
Y
100%
0%
X
W
?
60s
PiR
YOptm
dYOpt
Optimierung
Beedndet
OStar
+
Start
Adaption
t
t
Y
100%
0%
X
W
?
60
s
PiR
YOptm
dYOpt
Start Adaption
Optimierung
Beedndet
OStar
+
t
t
Y
100%
0%
X, W
W
X
?
60s
PiR
dYOpt
OStar
H
I
+
+
+
Start
Adaption
Optimierung
Beedndet
> 10% W0/W100
t
t
Y
100%
0%
X, W
W
X
?
60s
PiR
dYOpt
OStar
H
D
+
+
+
Start
Adaption
Optimierung
Beendet