Set value function
Text 1
Description
Range of settings
Default
Setpt
Set parameter
LC+
Bandwidth upper limit
0....9999
`-------´(off)
LC-
Bandwidth lower limit
0....9999
`-------´(off)
W0
Lower set-value limit for Weff
-999...9999
W100
Upper set-value limit for Weff
-999...9999
W2
Supplementary set value
-999...9999
Grw+
Set value gradient plus for W (w/min)
0.01...99.99
`-------´(off)
Grw-
Set value gradient minus for W (w/min)
0.01...99.99.
`-------´(off)
Grw2
Set value gradient W2 for W (w/min)
0.01...99.99
`-------´(off)
Alarm functions
Text 1
Description
Range of settings
Default
LIM1
Alarm1
LimL1
Lower limit
-999...99999
`-------´(off)
LimH1
Upper limit
-999...99999
`-------´(off)
Lxsd1
Switch difference
-999...99999
1
LIM2
Alarm2
LimL2
Lower limit
-999...99999
`-------´(off)
LimH2
Upper limit
-999...99999
`-------´(off)
Lxsd2
Switch difference
-999...99999
1
Standard algorithm
Text1
Description
Range of values
Default
Para
PID control parameter
XP1
Proportional range
0.1...999.9%
TN1
Reset time
0...9999 s
TV1
Rate time
0...9999 s
CPara
Control parameter
Tpuls
Min. pulse duration
0.1...999.9 s
0.5
Tm
Motor running time of the actuator
10...9999 s
60
Y2
Supplementary control value
-105...105%
50
Ymin
Lower manipulated variable limit
-105...105%
-105...105%
Ymax
Upper manipulated variable limit
-105...105%
-105...105%
Y0
Operating point of manipulated variable
-105...105%
0
Xsh
Neutral zone
0.2...999.9%
0.2
Xsh1
Neutral zone Xw<0 (only for continuous controller)
0.0...999.9%
1
Xsh2
Neutral Zone Xw>0 (only for continuous controller)
0.0...999.9%
1