9.7.1.3 Floor-to-Floor Correction
The unit works with automatic floor-to-floor correction taking constant courses independent of normal
floor-to-floor or long travel operations.
If the travel command (3) is taken away during the acceleration ramp, a floor-to-floor travel operation
is initiated. The shape of this floor-to-floor travel operation, however, can only be influenced
significantly using the parameters SC and R-SC if the drive command is cancelled early, so that there
is a sufficient distance available for the required shape of the curve. If the travel command is cancelled
a short time before the final speed is reached, the shape of the curve cannot be varied.
(1) High values for SC result in high speeds and correspondingly short
travel times.
(2) Low values for SC result in low speeds and correspondingly long
travel times.
With R_SC the rounding of the curve can be set. R=0: no rounding
R=1000: max. rounding
Note: The floor-to-floor travel operation is intended for high speed V4 only !
The distance of the floor-to-floor travel calculation to be covered is determined from V4 and B_V4.
Erw.Fahrkurve
R_SC 300ms
----------------------
○
Erw.Fahrkurve
SC 500
----------------------
○
Summary of Contents for FRC-F Series
Page 1: ...9 581 140 6 Page 1 VVVF Controller for Elevators FRC Q FRC F IMD...
Page 16: ...9 581 140 6 Page 16...
Page 17: ...9 581 140 6 Page 17...
Page 23: ...9 581 140 6 Page 23...
Page 85: ...9 581 140 6 Page 85...
Page 90: ...9 581 140 6 Page 90...
Page 122: ...9 581 140 6 Page 122...
Page 123: ...9 581 140 6 Page 123...
Page 124: ...9 581 140 6 Page 124...
Page 125: ...9 581 140 6 Page 125...