9.581.140-6
Page:
37
2 direction signals:
The desired direction is set by using terminals RU (terminal 51) and RO (terminal 52):
RU
RO
Response
0
0
none or stop
0
1
up-travel
1
0
down-travel
1
1
none or stop
If a direction signal fails during the travel operation, the controller starts a deceleration ramp and
stops. A change of direction signals during the travel operation results in a direct change of the
required value sign up to a speed of 25 rpm. In the case of higher speeds, the change of direction
command is ignored for safety reasons and a warning message is signalled on the display.
5.2.2.2.4 Control via floating contacts, internal control voltage
5.2.2.2.5 Control via floating contacts, external control voltage
Important Note!
The positive potential of the 24 V supply voltage of the control unit and the VVVF controller must not
be connected to one another, only the reference potential ( ground ) may be the same.
V3
floating contacts
Terminal
Drive Command V0 V1
15
16
V2
17
18
52
RO
50
VN
V4
19
RU
51
GS
53
GND
ext.
+24V
55
20
V3
external control v24V
Terminal
Drive Command
V1
V0
15
16
V2
17
18
24 VDC
+
-
52
RO
50
VN
V4
19
RU
51
GND
ext.
GS
53
+24V
55
20
Summary of Contents for FRC-F Series
Page 1: ...9 581 140 6 Page 1 VVVF Controller for Elevators FRC Q FRC F IMD...
Page 16: ...9 581 140 6 Page 16...
Page 17: ...9 581 140 6 Page 17...
Page 23: ...9 581 140 6 Page 23...
Page 85: ...9 581 140 6 Page 85...
Page 90: ...9 581 140 6 Page 90...
Page 122: ...9 581 140 6 Page 122...
Page 123: ...9 581 140 6 Page 123...
Page 124: ...9 581 140 6 Page 124...
Page 125: ...9 581 140 6 Page 125...