5.2.2.3.5 Faults / interruptions of safety circuit
Faults
If the inverter detects a fault, the
Fault Alarm Relay TÜ
is activated. As a result, terminals 3-4 are
opened. The ready output Terminal 59 is switched to 0V.
In addition, the brake (relay ZB / terminal 72) is closed and the main contactors (relay ZS / terminal
71) are opened.
Provided that the controller cancels the travel commands from the inverter in case of a fault, the
inverter performs an automatic error reset after 3 seconds. Then, it is ready for operation again.
Interruption of safety circuit
In case safety circuits are interrupted, the release signal (signal "GS") must be switched off on the
controller. As a result, the motor current is switched off directly. The controller closes the brake
immediately and performs a quick-stop ramp to zero within 0.5s.
Controller outputs an error message "GS failure during travel operation", if this monitoring function is
enabled in the service menu (see chapter 9.12.3.4).