9.581.140-6
Page:
116
12.2.2 Fastening the cables
The cable inlet is through the lower opening. On standard designs, the cable fastening plate is located on
the underside of the unit's mounting plate.
The cable fastening plate provides strain relief for the cables and screens the cables. Connect the cables as
follows:
unshielded cables:
•
Fasten with provided cable binders in the holes.
shielded cables:
•
Uncover cable shield.
•
Select appropriate cable clip.
•
Insert provided plate nuts at required points so that the smooth surface is facing upwards.
•
Using provided M4 screws, fasten clip in place in the plate nuts.
The sensor cable is also fed into the housing from below. The shield is grounded at the top at the connector.
12.2.3 Wiring
The mains supply line is connected to the terminals
"L1-L2-L3-PE"
. On units with integrated miniature circuit
breakers, the neutral wire must be connected to the terminal marked in blue.
The brake resistor lead is connected to the terminals
"RB"
and
"+"
and
"PE"
. In the case of units with
integrated braking resistance, no external wiring is required.
The motor lead is connected direct to the contacts marked
"U-V-W"
and the PE terminal.
The control cable is just plugged into the control system on
Plug&Play units.
Summary of Contents for FRC-F Series
Page 1: ...9 581 140 6 Page 1 VVVF Controller for Elevators FRC Q FRC F IMD...
Page 16: ...9 581 140 6 Page 16...
Page 17: ...9 581 140 6 Page 17...
Page 23: ...9 581 140 6 Page 23...
Page 85: ...9 581 140 6 Page 85...
Page 90: ...9 581 140 6 Page 90...
Page 122: ...9 581 140 6 Page 122...
Page 123: ...9 581 140 6 Page 123...
Page 124: ...9 581 140 6 Page 124...
Page 125: ...9 581 140 6 Page 125...