Page - 22 -
FLF 15000/1800/500
Panther 8x8 CA-7
© 2014
Technical Description
Overheating protection system
The pump case is equipped with a temperature sensor which
controls the overheating protection system.
The pump drain valve opens and the pilot lamp (H62) illuminates
on the external pump control panel and a warning is displayed on
the pump control screen in the cabin, when 60
°
Celsius is exceeded.
Water is discharged by the pump drain valve until the pump
housing is cooled down below 50
°
Celsius.
Counteraction: Open a pressure discharge valve for a short
period (until the temperature falls short of 50
°
C) to cool down
the pump or reduce the pump speed to idle.
ATTENTION !
To avoid critical operational circumstances and to react immediately
the operator must in easy reach of the pump control panel.
CAUTION !
Keep pump drainage area clear. Remember the possibility of hot
water being expelled!
Superstructure System Control
LCS Logic Control System
This operation and control system is designed to facilitate the
operation and supervision of several systems, mounted on the fire
fighting vehicle.
The main operating system is a CAN Bus (Controller Area Net-
work) with a serial data rate of 250 kB/sec. Data with high priority
will be sent first.
The fire fighting superstructure will be controlled via a display in
the drivers cabin and in the pump compartment.