Reference Manual
00809-0100-4664, Rev BA
January 2010
4-23
Rosemount 8712
Pulse Output Loop Test
The Pulse Output Loop Test allows you to drive the frequency output at
terminals 3 and 4 to a desired value. This capability allows you to check
auxiliary equipment prior to start-up. On the LOI the test will end after five
minutes if the transmitter is not returned to normal operation manually.
Digital Input / Digital Output
This menu is used to configure the optional digital input and digital output
parameters of the 8712 transmitter. Note that this configuration option is only
active if the auxiliary output suite (option code AX) was ordered or licensed in
the field.
DI/DO 1
Configure the auxiliary output channel 1. This controls the auxiliary channel 1
of the transmitter on terminals 9(+) and 10(-). Note that the transmitter must
have been ordered with the auxiliary output option (Model Code AX) or have
been licensed in the field in order to have access to this functionality.
Configure I/O 1
Configure channel 1 for either an Input or an Output.
Input – Channel 1 will be configured as a discrete input. Options are:
PZR – Positive Zero Return. When conditions are met to activate the input,
the transmitter will force the output to zero flow.
Net Total Reset – When conditions are met to activate the input, the
transmitter will reset the Net Total value to zero.
Output – Channel 1 will be configured as a discrete output. Options are:
Reverse Flow – The output will activate when the transmitter detects a
reverse flow condition.
Zero Flow – The output will activate when a no flow condition is detected.
Transmitter Fault – The output will activate when a transmitter fault
condition is detected.
Empty Pipe – The output will activate when the transmitter detects an
empty pipe condition.
Flow Limit 1 – The output will activate when the transmitter measures a
flow rate that meets the conditions established for the Flow Limit 1 Alert.
Flow Limit 2 – The output will activate when the transmitter measures a
flow rate that meets the conditions established for the Flow Limit 2 Alert.
Diagnostic Status Alert – The output will activate when the transmitter
detects a condition that meets the configured criteria of the Diagnostic
Status Alert.
Total Limit – The output will activate when the transmitter net total value
meets the conditions established for the Total Limit Alert.
Field Comm.
1, 4, 2, 2, 3
LOI Key
AUX. FUNCTION
Field Comm.
1, 4, 2, 3
LOI Key
AUX. FUNCTION
Field Comm.
1, 4, 2, 3, 1
Field Comm.
1, 4, 2, 3, 1, 1
Summary of Contents for 8712
Page 2: ......
Page 4: ......
Page 26: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 2 16 ...
Page 84: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 4 46 ...
Page 102: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 5 18 ...
Page 114: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 6 12 ...
Page 154: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 D 6 ...
Page 194: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 E 40 ...
Page 208: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 F 14 ...
Page 211: ......