Reference Manual
00809-0100-4664, Rev BA
January 2010
Rosemount 8712
C-10
Empty Pipe
Set the test criteria for the Empty Pipe condition. The factory default for this
value is set to three percent with limits configurable between one and ten
percent.
8714i Meter Verification Test Scope
The 8714i Meter Verification can be used to verify the entire flowmeter
installation, or individual parts such as the transmitter or sensor. This
parameter is set at the time that the 8714i Meter Verification test is initiated.
All
Run the 8714i Meter Verification test and verify the entire flowmeter
installation. This parameter results in the calibration verification performing
the transmitter calibration verification, tube calibration verification, coil health
check, and electrode health check. Transmitter calibration and tube
calibration are verified to the percentage associated with the test condition
selected when the test was initiated.
Transmitter
Run the 8714i Meter Verification test on the transmitter only. This results in
the verification test only checking the transmitter calibration to the limits of the
test criteria selected when the 8714i Meter Verification test was initiated.
Sensor
Run the 8714i Meter Verification test on the sensor only. This results in the
verification test checking the sensor calibration to the limits of the test criteria
selected when the 8714i Meter Verification test was initiated, verifying the coil
circuit health, and the electrode circuit health.
8714i Meter Verification
Test Results Parameters
Once the 8714i Meter Verification test is initiated, the transmitter will make
several measurements to verify the transmitter calibration, tube calibration,
coil circuit health, and electrode circuit health. The results of these tests can
be reviewed and recorded on the calibration verification report found on
page C-16. This report can be used to validate that the meter is within the
required calibration limits to comply with governmental regulatory agencies
such as the Environmental Protection Agency or Food and Drug
Administration.
HART Fast Keys
1, 2, 3, 3, 4, 3
AMS Tab
8714i
HART Fast Keys
1, 2, 3, 3, 1, 1
AMS
Context Menu, Diagnostics and Tests, 8714i Meter Verification
HART Fast Keys
1, 2, 3, 3, 1, 2
AMS
Context Menu, Diagnostics and Tests, 8714i Meter Verification
HART Fast Keys
1, 2, 3, 3, 1, 3
AMS
Context Menu, Diagnostics and Tests, 8714i Meter Verification
Summary of Contents for 8712
Page 2: ......
Page 4: ......
Page 26: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 2 16 ...
Page 84: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 4 46 ...
Page 102: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 5 18 ...
Page 114: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 6 12 ...
Page 154: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 D 6 ...
Page 194: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 E 40 ...
Page 208: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 F 14 ...
Page 211: ......