Energy and time conversion example
To find the Base per Custom relationship for a custom unit of thousands of BTU per day (kBtud) and a
base unit of BTU per hour (Btu/h), input the following:
Custom Unit = kBtud
Base Unit = Btu/h
Because:
1 kBtu (Thousands of BTU)= 1000 Btu and
1 d (Day) = 24 h (Hours)
Then:
1 kBtud =
⫻
⫻
= 41.6667 Btu/h
1 kBtud = 41.6667 Btu/h
Therefore:
Base per Custom =
=
= 41.6667
Figure 2-33. Energy Rate Custom Units - Energy and Time Conversion Example
Under the
Low Flow Cutoff
heading, edit the current
Minimum DP Value
as needed. The unit for this
value is the user-selected DP unit. If the measured DP value is less than the minimum DP value, the
transmitter will calculate the energy value to be zero.
The
Sensor Limits
and
Minimum Span
can be viewed under the
Energy Rate Sensor Limits
heading.
1 kBtu
⋅
1 d
⋅
--------------------
1000 Btu
⋅
1 kBtu
⋅
---------------------------
1 d
⋅
24 h
⋅
--------------
Number of Base Units
1
x
Custom
x
Unit
----------------------------------------------------------------------
41.6667 Btu h
⁄
⋅
1 kBtud
⋅
-------------------------------------------