![Rosemount 3051S Series Reference Manual Download Page 113](http://html.mh-extra.com/html/rosemount/3051s-series/3051s-series_reference-manual_1487385113.webp)
105
Reference Manual
00809-0100-4803, Rev GA
Operation and Maintenance
September 2017
Operation and Maintenance
Note
Due to the sensitivity of the Range 1 DP Sensor, extra steps are required to optimize performance. It is
necessary to temperature soak the assembly using the following procedure.
1. After replacing O-rings on DP Range 1 transmitters and re-installing the process flange, expose the
transmitter to a temperature of 185 °F (85 °C) for two hours.
2. Re-tighten the flange bolts in a cross pattern.
3. Again, expose the transmitter to a temperature of 185 °F (85 °C) for two hours before calibration.
4.6.6
SuperModule assembly
To reorder an upgrade or replacement SuperModule assembly, use the Rosemount 3051SMV
but replace the housing option code with ‘00’.
1. Remove the housing assembly per
“Upgrading or replacing the housing assembly including feature
board electronics” on page 100
2. Remove currently installed SuperModule assembly from process flange per
.
3. Reassemble replacement or upgraded SuperModule assembly to process flange per
.
4. Reassemble the housing assembly per
“Upgrading or replacing the housing assembly including