![Rockwell Automation Allen-Bradley PowerFlex 20P Manual Download Page 93](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-20p/allen-bradley-powerflex-20p_manual_1475484093.webp)
Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
93
Access Procedures
Chapter 3
5.
Loosen the two bolts that secure the fuse to the busbar and SCR leg
terminal. Rotate the top of the fuse out and downward and pull the fuse
off of the lower bolt and out of the drive.
Install the Armature Leg Fuse
Install the armature leg fuse in the reverse order of removal.
•
Tightening torque for the fuse bolt is 45 N•m (398 lb•in).
•
Install the existing fuse switch on the fuse body using the existing
hardware. Verify that all wires are properly connected to the fuse switch.
5
5
5