Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
Chapter 2
Component Test Procedures
Figure 9 - Field Terminal Block and Field Fuse Locations
8.
Remove the cable from connector XP on the pulse transformer circuit
board.
9.
Check the gate cathode junction of the field SCR/dual diode module.
With the digital multimeter set to “diode test” measure the resistance
across the modules (lead orientation is not critical). See
If a low resistance is detected, replace the SCR/dual diode module.
Table 11 - SCR/Dual Diode Module Gate Cathode Junction Measurements
Measure from…
To…
Nominal meter reading:
XP1
XP2
10…20
XP3
XP4
Bottom, Left Side of Drive
Top, Left Side of Control Panel
Shown with control cover
removed. Remove control cover
to access terminals.
Field AC input terminals (U1, V1) at top
of fuse holder
C1
D1
Field fuses (FU1, FV1)