Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
Chapter 3
Access Procedures
Series A Fan Assembly
Removal and Installation
Remove the Series A Fan Assembly
1.
Read the General Safety Precautions on page
2.
Remove power from the drive. See Remove Power from the Drive on page
3.
Remove the top terminal cover from the drive. See Remove the Protective
Covers on page
4.
Loosen, but do not remove, the six hexalobular screws that secure the top
airflow plate to the drive, then slide the plate forward to lift it off the
screws.
Note: The airflow plate cannot be removed from the drive unless the AC
input wiring and busbar extensions (if installed) are removed.
5.
Remove the wires connected to the terminal block at XF on the fan circuit
board (at the top of the drive, to the left of the fan blower). Cut the cable
ties that secure the fan blower motor wires to the fan capacitor wires.
Tightening torque:
1.5 N
•
m (13 lb
•
in)
T15
4
4
Top View of Drive
Fan Circuit Board
IMPORTANT
Mark all connections and wires before removal to avoid incorrect
wiring during reassembly.
V2
V1
C1
PE
XF
XC
XE
K1
5