![Rockwell Automation Allen-Bradley PowerFlex 20P Manual Download Page 30](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-powerflex-20p/allen-bradley-powerflex-20p_manual_1475484030.webp)
30
Rockwell Automation Publication 20P-TG004C-EN-P - September 2021
Chapter 2
Component Test Procedures
Table 2 - SCR Anode to Cathode Junction Measurements for Regenerative Drives
Figure 7 - Regenerative Drive SCR Module Layout
For SCR…
Measure from
Terminal…
To Terminal… Nominal meter reading:
1
U
C
“open circuit” or “megaOhms” range
4
U
D
2
V
C
5
V
D
3
W
C
6
W
D
01
U
C
04
U
D
02
V
C
05
V
D
03
W
C
06
W
D
SCR 1 - G
SCR 1 - K
SCR 01 - G
SCR 01 - K
SCR 04 - G
SCR 04 - K
SCR 4 - G
SCR 4 - K
Front Gate Lead
Terminal Block
SCR 2 - G
SCR 2 - K
SCR 02 - G
SCR 02 - K
SCR 05 - G
SCR 05 - K
SCR 5 - G
SCR 5 - K
SCR 3 - G
SCR 3 - K
SCR 03 - G
SCR 03 - K
SCR 06 - G
SCR 06 - K
SCR 6 - G
SCR 6 - K
Phase U
Rear Gate Lead
Terminal Block
Phase U
Rear Gate Lead
Terminal Block
Phase V
Front Gate Lead
Terminal Block
Phase V
Front Gate Lead
Terminal Block
Phase W
Rear Gate Lead
Terminal Block
Phase W