40
Rockwell Automation Publication 2711T-QS002C-EN-P - March 2019
Second Generation MobileView Tethered Operator Terminal
11. Press the second generation MobileView terminal desktop to access EWF Manager and
enable EWF; see
for how to enable EWF.
After you enable EWF, the MobileView 2711T terminal automatically restarts.
12. If FactoryTalk View ME Station was configured in
to automatically start after any
second generation MobileView 2711T terminal startup or reboot, then the application
automatically starts after
If FactoryTalk was not configured to automatically start, then you must press the
FactoryTalk View ME Station icon on the second generation MobileView terminal
desktop to load and run the application.
Right-click Touch Screen Functionality and FactoryTalk View ME Station
If your FactoryTalk View ME Station uses momentary push buttons and you require long press
times to activate those buttons, then the right-click touch screen functionality within the
MobileView operating system must be disabled. By default, right-click functionality is enabled
for the touch screen.
To disable right-click touch screen functionality, perform the following steps.
1.
From the second generation MobileView 2711T terminal desktop, press Touch
Configuration.
IMPORTANT
Do not press the Exit button (F8) in FactoryTalk View ME Station before you access
EWF Manager on the MobileView terminal desktop.
IMPORTANT
EWF must be disabled before you change right-click functionality, and then enabled
afterwards. For more information, see