![Rockwell Automation Allen-Bradley DriveLogix 5730 User Manual Download Page 59](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-drivelogix-5730/allen-bradley-drivelogix-5730_user-manual_1475407059.webp)
Placing and Configuring Local I/O
3-11
inhibit or 0 to uninhibit). Use a SSV instruction to write the Mode attribute
back to the module. For example:
Sending Module Configuration Information
The controller sends module configuration information once module
connections are established.
The GSV instruction gets the current status of the module named “input_module.” The SSV instruction sets the state of “input_module” as either
inhibited or uninhibited.
When on, inhibits the module.
When off, uninhibits the module.
!
ATTENTION:
If you make a configuration change to any
module in the system do one of the following to resend module
configuration data:
•
cycle power to the controller
•
inhibit and then uninhibit the bus
•
inhibit and then uninhibit the individual module
•
send a MSG instruction of type Module Reconfigure (for
information on configuring a MSG to send configuration data,
see the Logix5000 Controllers General Instructions Reference
Manual, publication 1756-RM003)