During the process of placing and configuring I/O you will need to connect
or disconnect a programming or network cable at the controller. You should
do this only if the drive is de-energized.
1.
Turn off and lock out input power. Wait five minutes.
2.
Verify that there is no voltage at the drive’s input power terminals.
3.
Measure the DC bus voltage at the +DC & -DC terminals on the Power
Terminal Block. The voltage must be zero.
4.
Connect or disconnect the programming or network cable.
5.
Turn power back on and proceed with placing and configuring the I/O.
Understanding How the
DriveLogix5730 Supports
I/O
The DriveLogix5730 controller supports up to 2 banks of modules with a
maximum of 8 modules per bank. You must distribute the modules within
each bank so that no more than 4 modules are on either side of the power
supply.
!
ATTENTION:
Severe injury or death can result from electrical
shock or burn. Verify that the voltage on the bus capacitors has
discharged before connecting to the communication ports.
Measure the DC bus voltage at the +DC & -DC terminals on the
Power Terminal Block. The voltage must be zero.
Summary of Contents for Allen-Bradley DriveLogix 5730
Page 6: ...4 ...
Page 10: ...p 4 Notes ...
Page 22: ...1 12 What is DriveLogix5730 Notes ...
Page 68: ...3 20 Placing and Configuring Local I O Notes ...
Page 134: ...6 36 Communicating with Devices on an EtherNet IP Link Notes ...
Page 182: ...9 10 Communicating with Devices on a DH485 Link Notes ...
Page 200: ...B 10 Access Procedures Notes ...
Page 205: ......
Page 206: ......
Page 207: ......