8-8
Communicating with Devices on an DeviceNet Link
Module Command Array
The module command array is the primary control interface between your
control program and the module. In RSLogix 5000 software, the
CommandRegister tag structure is as follows:
Output Word
Bit
Description
Behavior
0
0
Run
This bit controls when the module scans its mapped slave devices. When
set (1), the scanner will process I/O data as defined by its scanlist. To
actually scan the network the Fault and Disable Network command bits
must be clear (0).
1
Fault
When set, the scanner’s I/O mode will be Halt; messaging will still operate.
The fault bit is primarily used to artificially set the slave devices into a fault
state due to some event or condition within the control program.
2
Disable Network
When set, the scanner is functionally removed from the network.
3
HaltScanner
When set, the scanner stops scanning its mapped slave devices.
4
Reset
Restarts access to the DeviceNet network.