![Rockwell Automation Allen-Bradley DriveLogix 5730 User Manual Download Page 125](http://html.mh-extra.com/html/rockwell-automation/allen-bradley-drivelogix-5730/allen-bradley-drivelogix-5730_user-manual_1475407125.webp)
Communicating with Devices on an EtherNet/IP Link
6-27
Configuring the MSG Instruction that Identifies the Mail Relay Server
In this field:
Enter:
Service Type
Set Attribute Single
Instance
1
Class
32f
Attribute
5
Source Element
the STRING tag that contains the IP address or host name of the mail relay server
In this example, enter EmailConfig
Source Length
the number of characters in the IP address or host name of the mail server plus 4
In this example, enter 17 (13 characters in the IP address 10.88.128.111 + 4)
1.
On the Configuration tab of the Message Configuration, fill out the following fields:
2.
On the Communication tab of the Message Configuration, set the Path (e.g. browse for the
Embedded EtherNet Port).
Click Apply.
Click OK.